The following information is a comprehensive fuel cleanliness study of our bulk storage fuel filtration systems over the past few years. All samples were taken from various tank nozzles and filtration systems around the United States.
Predictive Maintenance services is a leading fuel analysis lab and their maximum allowable ISO diesel fuel cleanliness is ISO 20/19/15 maximum or cleaner.
Sample # 1 from the fuel nozzle into the tank ISO Cleanliness 20/18/16
Sample # 1 out of the PFS Ultimate system ISO Cleanliness 16/14/12
Sample # 2 from the fuel nozzle into the tank ISO Cleanliness 20/18/17
Sample # 2 out of the PFS Ultimate system ISO Cleanliness 16/14/12
Sample # 3 from the fuel nozzle into the tank ISO Cleanliness 23/21/19
Sample # 3 out of the PFS Ultimate system ISO Cleanliness 18/16/16
Sample # 4 from the fuel nozzle into the tank ISO Cleanliness 21/18/14
Sample # 4 out of the PFS Ultimate system ISO Cleanliness 19/16/12
Sample # 5 from the fuel nozzle into the tank ISO Cleanliness 21/18/14
Sample # 5 out of the PFS Ultimate system ISO Cleanliness 19/16/12
Sample # 6 from the fuel nozzle into the tank ISO Cleanliness 23/21/19
Sample # 6 out of the PFS Ultimate system ISO Cleanliness 18/16/13
Sample # 7 from the fuel nozzle into the tank ISO Cleanliness 20/19/15
Sample # 7 out of the PFS Ultimate system ISO Cleanliness 16/14/11
Sample # 8 from the fuel nozzle into the tank ISO Cleanliness 25/23/14
Sample # 8 out of the PFS Ultimate system ISO Cleanliness 21/18/14
Sample # 9 from the fuel nozzle into the tank ISO Cleanliness 24/21/15
Sample # 9 out of the PFS Ultimate system ISO Cleanliness 22/19/15
The following information is a comprehensive list of hydraulic fluid analysis before and after results.
Most samples were taken after 200 hours of filtration and the customer changes filters every six months.
Sample # 1 Brand new hydraulic fluid ISO 18/14
Sample # 1 Before filtration ISO Cleanliness 19/12
Sample # 1 After 200 hours of filtration ISO Cleanliness 15/10
Sample # 2 Before filtration ISO Cleanliness 23/21/19
Sample # 2 After 200 hours of filtration ISO Cleanliness 17/15/13
Sample # 3 Before filtration ISO Cleanliness 23/20/17
Sample # 3 After 200 hours filtration ISO Cleanliness 19/16/13
Sample # 4 Before filtration ISO Cleanliness 20/16
Sample # 4 After 200 hours of filtration ISO Cleanliness 16/11
Sample # 5 Before filtration ISO Cleanliness 21/17
Sample # 5 After 200 hours of filtration ISO Cleanliness 16/13
Sample # 5 After 7 months of filtration ISO Cleanliness 17/14
Sample # 5 After 15 months of filtration ISO Cleanliness 17/13
Sample # 6 Before filtration ISO Cleanliness 20/18/15
Sample # 6 After 200 hours filtration ISO Cleanliness 16/15/12
Sample # 7 Before filtration ISO Cleanliness 21/17/15
Sample # 7 After 200 hours of filtration ISO Cleanliness 15/14/11
Sample # 7 After 19 months of filtration ISO Cleanliness 17/15/12
Sample # 7 After 24 months of filtration ISO Cleanliness 17/15/12
After 200 hours of filtration with an Ultimate by-pass filtration systems installed the fluid is many times cleaner than brand new fluid. As long as the customer changes the PFS 1 micron depth-type filter element every six months the fluid will last for years and the customer will virtually eliminate failures to pump, motors, servo valves, proportional valves, and other hydraulic components due to water and solid particles.